TMG transformer type |
Power, kVA 25 |
Nominal voltage of LV winding, kV 0.4 |
Rated voltage of HV winding, kV 10 |
Diagram and group of U/Un-0 windings
connection; D/Un-11 |
Type of PBV voltage control |
Voltage control range ± 2x2.5% |
Material of aluminium windings |
Short circuit losses, Rkz W 600; 680 |
Idling losses, RxW 100 |
Short-circuit voltages, Uк % 4,5; 4,7 |
Idling current, I0 % 2,4 |
Climatic design and category of
accommodation У1 |
Degree of protection IP00 |
Overall dimensions (mach); |
Length, mm 844 |
Width, mm 515 |
Height, mm 1036 |
Weight, kg full/oil 282/76 |
Installation dimensions 450x400 |
Availability of transport rollers Yes |
No gas relay available |
Availability of custom temperature sensor |
Availability of manovacoummeter by order |
No safety valve |