Oil Type Transformer ТМГ-1600/6 - 0.4 kV Nominal Power 1600 KVA
- Brand:Alageum Electric
- Model: ТМГ-1600/6 - 0,4 кВ
- SKU: 10019
- Country of Origin: Kazakhstan
- Availability: Pre-Order
-
56014.30₾
Transformer, Oil type TMG-1600/6 - 0.4 kV
Type of transformer TMG
Power, kVA 1600
Rated voltage of the LV winding, kV 0.4
Rated voltage of HV winding, kV 6(10)
Scheme and group of connection of windings U / Un-0; D/Un-11
Type of voltage regulation PBV
Voltage regulation range +-2x2.5%
Winding material aluminum
Short circuit losses, Rkz W 18000
No-load losses, RxW 1710
Short circuit voltage, Uk % 6.0
No-load current, Io% 0.3
Climatic version and placement category U1
Rated frequency, Hz 50
Overall dimensions (max);
Length, mm 1954
Width, mm 1270
Height, mm 1981
Weight, kg full/oil 3981/770
Mounting dimensions 1070x1070
Availability of transport rollers yes
No gas relay
Optional temperature sensor
Availability of a manovacuummeter on request
No safety valve
Insulation class A
External insulation category II (GOST 9920-89)
Ambient temperature from -45°С to +40°С
Altitude above sea level, m 1000
Type of transformer TMG
Power, kVA 1600
Rated voltage of the LV winding, kV 0.4
Rated voltage of HV winding, kV 6(10)
Scheme and group of connection of windings U / Un-0; D/Un-11
Type of voltage regulation PBV
Voltage regulation range +-2x2.5%
Winding material aluminum
Short circuit losses, Rkz W 18000
No-load losses, RxW 1710
Short circuit voltage, Uk % 6.0
No-load current, Io% 0.3
Climatic version and placement category U1
Rated frequency, Hz 50
Overall dimensions (max);
Length, mm 1954
Width, mm 1270
Height, mm 1981
Weight, kg full/oil 3981/770
Mounting dimensions 1070x1070
Availability of transport rollers yes
No gas relay
Optional temperature sensor
Availability of a manovacuummeter on request
No safety valve
Insulation class A
External insulation category II (GOST 9920-89)
Ambient temperature from -45°С to +40°С
Altitude above sea level, m 1000
Tags: ТМГ-1600/6 - 0, 4 кВ